4. Select a setpoint and click
Learn
.
The
Global Setpoint Learning
screen is displayed.
5. Select the setpoint tabs to view existing configured or learned setpoint
information.
6. Click
Setup
.
The
Alarm Learning Setup
screen is displayed.
Setpoint learning parameters
Parameter
Value/Range
Description
Install mode
Automatic,
Manual
•
Automatic: the learned values are automatically
applied.
•
Manual: the learned values are stored for you to
review and enter.
Duration
1-365
Days for maximum learning duration.
7. Configure the learning parameters for each setpoint and click
Save
.
8. Click
Start All
to begin setpoint learning for all setpoints. Click
Yes
to confirm
or
No
to cancel.
–
Learning status and time remaining are indicated in the Learning Status
box.
–
Click
Abort
to stop learning for a specific setpoint. To stop all setpoint
learning, repeat for each setpoint tab.
9. Apply the learned setpoint values:
–
Automatic: the setpoint values are automatically applied unless the
learning process has issues or the learned values are invalid.
–
Manual: navigate to
Alarming > Setpoints
and click
Learn
. On each
setpoint tab, click
Install
to apply the learned values to that setpoint.
NOTE:
If you click
Install
while learning is in progress (in either manual or
automatic installation mode), it stops the learning process and prompts
you for confirmation that you want to stop learning and install the learned
values. Once you confirm, the learned values are automatically installed
or prepared for manual installation.
Implementing sag/swell limit learning using ION Setup
You can use ION Setup to implement voltage sag/swell learning, which analyzes
your power system and recommends settings.
NOTE:
Your meter’s power system must be stable in order to learn valid sag/
swell limits.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Alarming > Sag/Swell
.
7EN05-0390-00
135