For active high priority alarms, the meter’s display will also flash until the alarm is
acknowledged. There is also an alarm LED to indicate the meter’s alarm
condition.
Alarm
Alarm icon
Alarm icon flash
Alarm LED
Meter display
Active high
Red solid bell
Flash if not
acknowledged
•
Flash if not
acknowledged
•
Steady if
acknowledged
Flash if not
acknowledged
Active medium
Yellow solid bell
Flash if not
acknowledged
•
Flash if not
acknowledged
•
Steady if
acknowledged
No flash
Active low
Blue solid bell
Flash if not
acknowledged
•
Flash if not
acknowledged
•
Steady if
acknowledged
No flash
Historic high
Red outline bell
Flash if not
acknowledged
•
Flash if not
acknowledged
•
Steady if
acknowledged
No flash
Historic medium
Yellow outline bell
Flash if not
acknowledged
•
Flash if not
acknowledged
•
Steady if
acknowledged
No flash
Historic low
Gray solid bell
No flash
Off
No flash
No active or
unacknowledged alarms
Gray solid bell
No flash
Off
No flash
If there are multiple active alarms, the meter displays the alarm condition
associated with the most important active alarm. If there are multiple
unacknowledged historic alarms, the meter displays the alarm condition
associated with the most important unacknowledged historic alarm.
NOTE:
To stop an alarm from being displayed without impacting other
metering features, set the alarm priority to
Info Only
.
Default alarms
Your meter comes with default alarms. Some alarms are enabled by default.
NOTE:
Some alarms require configuration in order to operate.
Name
Priority
Description
Default
Current Sag Ph1 - 3
High
Current sag alarms for phase 1, 2, 3
Disabled
Current Swell Ph1 - 3
High
Current swell alarms for phase 1, 2, 3
Disabled
Sag/Swell
High
Voltage sag/swell alarm
Disabled
Over I unbal
Medium
Over unbalanced current alarm
Disabled
Over V unbal
Medium
Over unbalanced voltage alarm
Disabled
Over THD V1 - 3
Medium
Over total harmonic distortion (THD) voltage alarms
Enabled
Over kW (P) sd
Medium
Over kW sliding demand alarm
Disabled
Over I a - c, (1 -3) 4
Medium
Over current alarms
Disabled
V1 - V3 Setpoint
Medium
Voltage setpoint alarms
Disabled
Freq Setpoint
Medium
Frequency setpoint alarm
Enabled
4-30 Volt Intrp Ph1 - 3
Low
4-30 voltage interruption power quality alarms
Enabled
126