Standard and advanced security features
Security settings allow you to configure security features on your meter.
Parameter
Standard/
advanced
Details
Meter password
Standard/
advanced
The meter’s password is used to confirm user access
when configuring the meter through the display or over
communications.
The default meter password is 0 (zero).
Active web
server
Standard/
advanced
This option allows you to enable or disable your meter’s
webpages.
Allow web server
programming
Standard/
advanced
This option allows you to enable or disable the ability to
configure your meter using the meter’s webpages.
NOTE:
To enable
Allow web server programming
,
you must have active web server enabled.
Allow Modbus
programming
Advanced only
This option can only be enabled in advanced security and
is disabled for standard security.
Allow front panel
programming
Standard/
advanced
This option allows you to enable or disable the ability to
configure your device using the display.
Allow
broadcasting
time
synchronization
Advanced only
This option can only be disabled in advanced security and
is enabled for standard security.
Protocol lockout
Standard/
advanced
This option allows you to configure the number of access
attempts before lockout, lockout duration and meter
access event priorities.
Advanced security user configuration
Advanced security allows you to configure users with specific access levels and
passwords.
Security configuration process
The security configuration process has four basic steps: review security
recommendations, set basic security options, configure communications protocol
lockout settings, and configure users.
1. Review security recommendations
2. Set basic security options
•
Change the meter password.
•
Disable broadcasting time synchronization (advanced security only).
•
Enable/disable display (front panel) and Webserver programming.
•
Enable/disable Modbus programming (advanced security only).
3. Configure communications protocol lockout options
a. Configure protocol-specific settings:
•
Set the number of attempts before the protocol is locked out.
•
Set the session timeout.
b. Configure global lockout settings:
•
Enter a lockout duration.
•
Set the priority of meter access events.
4. Configure users (advanced security only)
•
Determine user access.
•
Set user passwords.
7EN05-0390-00
115