8 Communication
8.3 I/O Mirror
157
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
8.3
I/O Mirror
8.3.1
Ethernet Communication
8.3.1.1
I/O Mirror Client
Prerequisite
Under serial communication, no I/O mirror mode must be parameterized.
Parameterization
The following parameters can be parameterized for Ethernet communication for the I/O mirror client mode, see
also chapter 6.3.3.6:
Table 8-5
I/O Mirror Client Settings at Ethernet Communication
NOTE
The operational indications output by the SICAM I/O Unit are described in detail in chapter 12.
Parameter
Default Settings
Settings
IP address
192.168.0.55
Any
Subnet mask
255.255.255.0
Any
Default gateway
192.168.0.1
Any
Operating mode
I/O mirror client
-
Server IP address
192.168.0.56
Any
Server port
51000
10000 to 65535
Response timeout
3 * 10 ms
0 ms = invalid
10 ms to 60 000 ms