6 Operation
6.6 Examples for Parameterization
117
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
6.6.1
Application as Modbus Server via the Ethernet Connection
Conceptual Formulation
✧
Carry out parameterization, using the factory settings.
✧
Parameterize the threshold voltages of the 6 binary inputs.
✧
Parameterize the messages and modes of the 6 binary outputs (relay outputs).
✧
Use the hardware configuration according to Figure 5-3 without I/O expansion.
Factory Setting of the Ethernet Communication via Modbus TCP
Figure 6-64
Default Setting Ethernet Communication
NOTE
Please note the Modbus data mapping in chapter 8.2.8.