Device Data
Supply Voltage via a Wide-Range Power-Supply Unit
Auxiliary voltage – direct voltage
DC 24 V to 250 V
Permissible voltage range
DC 19 V to 300 V
Power consumption
< 4 W
Permissible AC ripple voltage,
Peak-peak
≤ 12 % at the rated voltage, IEC 60255-1
Stored-energy time for outage/short circuit of the
auxiliary voltage
≥ 50 ms
Auxiliary voltage – alternating voltage
AC 110 V to 230 V, 50 Hz/60 Hz
Permissible voltage range
AC 99 V to 253 V
Power consumption
< 10 VA
Connection
2-pole screw terminal
Signal Relay (Life Contact)
Contact
1 change-over contact
Switching power
– ON
– OFF
1000 W, 1000 VA
30 VA; 40 W ohmic
Contact voltage
250 V
Permissible current per contact
5 A continuously,
30 A for 0.5 s
Unsuitable for isolating supply voltages
Connection
3-pole screw terminal
Terminals for Auxiliary Voltage (Life Contact), and Line
Rated line cross-section
0.2 mm
2
to 2.5 mm
2
solid,
0.25 mm
2
to 1.5 mm
2
with bootlace ferrule
Stripped length
9 mm
Tightening torque
0.4 Nm to 0.5 Nm
Internal Fuses
Not interchangeable
T 1.6 A at AC 250 V acc. to IEC 60127
Not interchangeable, secondary
F 2 A at AC 125 V acc. to UL 248-14
6.1
Technical Data
6.1 Device Data
36
Accessories, Communication Converter - Copper/Synchronous Interface, Manual
C53000-B1174-C190-1, Edition 01.2022