Features
The CC–CO for pilot wire pairs has the following features:
Asynchronous transfer rate from 300 Bd to 38.4 kBd (max. 52 kBd) permissible at it’s
input FO-interface. No settings in CC–CO required.
Signal line to the protection device via fibre optic cable to an integrated FO module.
Maximum length of the fibre optic cable for the connection of protection device
↔
CC–CO is 1.5 km (0.93 mile) with 62.5/125 µm multimode, ST-plug.
Maximum cable length for the connection of CC–CO (Master)
↔
CC–CO (Slave) for
AWG 19 is 12.1 km (7.56 miles).
Maximum cable length for the connection of CC–CO (Master)
↔
CC–CO (Slave) for
AWG 22 is 8 km (5 miles).
Maximum cable length for the connection of CC–CO (Master)
↔
CC–CO (Slave) for
AWG 26 is 4.4 km (2.75 miles).
Further distances for other AWG/cross-sections see under Technical Datas.
Wide-area power supply unit for DC: 24 V to 250 V (voltage limit DC: 19 V to 300 V) and
AC: 115 V to 250 V (range AC: 92 V to 286 V).
Power consumption < 4 W / < 10 VA.
Monitoring of the auxiliary supply voltage and of the internal logic devices.
Housing, dimensions 188 mm × 120 mm × 55 mm
(7.4 in × 4.7 in × 2.2 in) (W × D × H) for rail mounting.
Direct connection to the transmission line (pilot wire pair) with 5 kV isolation voltage.