Device Data
Auxiliary Voltage V
aux
Terminal
2-pole terminal (Phoenix)
Rated auxiliary voltage
– Direct voltage
DC 24 V to 250 V
– Alternating voltage
AC 110 V to 230 V/45 Hz to 65 Hz
Permissible voltage range
– Direct voltage
19 V to 300 V
– Alternating voltage
92 V to 286 V
Power consumption
– Direct voltage
Max. 3 W
– Alternating voltage
Max. 3.5 VA
Operating state display
1 green LED (RUN)
Fuses
Soldered in place
T1.25 A
Protection class
II
Structural Variant
Housing
Plastic (EC 90)
Dimensions
See the outline drawings at
Weight
About 250 g
Degree of protection according to EN 60529:
– Housing
IP 20; plastic
– Terminals
IP 20
Safety
As per DIN EN 61010 Part 1, overvoltage category
III (AC 3.7 kVA/DC 5.2 kV)
Degree of pollution
2
Fire-resistance rating as per UL 94
V0
5.1
Technical Data
5.1 Device Data
40
Accessories, Binary signal transmitter 2-channel, Manual
C53000-G9050-C607-1, Edition 09.2019
Summary of Contents for 7XV5653-0BA00
Page 12: ...12 Zubehör Binärsignalübertrager 2 kanalig Handbuch C53000 G9050 C607 1 Ausgabe 09 2019 ...
Page 30: ...30 Zubehör Binärsignalübertrager 2 kanalig Handbuch C53000 G9050 C607 1 Ausgabe 09 2019 ...
Page 40: ...40 Zubehör Binärsignalübertrager 2 kanalig Handbuch C53000 G9050 C607 1 Ausgabe 09 2019 ...
Page 56: ...6 Accessories Binary signal transmitter 2 channel Manual C53000 G9050 C607 1 Edition 09 2019 ...
Page 62: ...12 Accessories Binary signal transmitter 2 channel Manual C53000 G9050 C607 1 Edition 09 2019 ...
Page 80: ...30 Accessories Binary signal transmitter 2 channel Manual C53000 G9050 C607 1 Edition 09 2019 ...