3.13 Voltage Protection: Under/Over Frequency (81)
Optionally six under/over frequency elements are provided.
Frequency elements are blocked if the measured voltage falls below the
81 U/V Guard
setting.
The sense of the element (under-frequency or over-frequency) is set by the
81-n Operation
setting.
81-n Setting
sets the pick-up frequency for the element.
An output is given after elapse of the
81-n Delay
setting.
The
81-n Hysteresis
setting allows the user to vary the pick-up/drop-off ratio for the element.
Operation of the under/over frequency elements can be inhibited from:
Inhibit 81-n
A binary or virtual input.
81-n U/V Guarded
Under voltage guard element.
User Inhibit
Reylogic (graphical logic).
Figure 3-20 Logic Diagram: Under/Over Frequency Detector (81)