3.10 Voltage Protection: Over Fluxing (24)
Optionally, three over fluxing elements are provided – 2 x 24DT and 1 x 24IT Char elements.
The 24DT Elements have a DTL characteristic.
24DT Setting
sets the pick-up level and
24DT Delay
the follower
time delay. An output is given if the Volts/Hertz ratio is above setting for the duration of the delay. The
24DT-n
Hysteresis
setting allows the user to vary the pick-up/drop-off ratio for the element.
The 24IT Element has a user definable shape.
24Xn Point Setting
sets the over fluxing (V/f) level for up to 7 user definable points.
24Yn Point Setting
sets the operate time for each of the defined points.
The
24IT Reset
setting can apply a,
definite time delayed
reset.
Figure 3-16 Inverse Over-fluxing Characteristic (24IT)
Operation of the over fluxing elements can be inhibited from:
Inhibit 24IT
A binary or virtual input.
Inhibit 24DT-n
A binary or virtual input.
User Inhibit
Reylogic (graphical logic).
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......