Chapter 3) 7SR242 Duobias Performance Specification
©2015 Siemens Protection Devices Limited
Chapter 3 Page 25 of 50
2.5.6 Operate and Reset Time (46IT)
Attribute
Value
Starter operate time ( 2
xIs
)
35 ms, 10ms
t
op
Operate time
char
= IEC-NI,
IEC-VI,
IEC-EI,
IEC-LTI
Tm
K
t
Is
I
op
1
, 5 % absolute or 50 ms,
for char = IEC-NI : K = 0.14, = 0.02
IEC-VI : K = 13.5, = 1.0
IEC-EI : K = 80.0, = 2.0
IEC-LTI : K = 120.0, = 1.0
char
= ANSI-MI,
ANSI-VI,
ANSI-EI
Tm
B
A
t
P
Is
I
op
1
, 5 % absolute or 50 ms,
for char = ANSI-MI : A = 0.0515, B = 0.114, P = 0.02
ANSI-VI : A = 19.61, B = 0.491, P = 2.0
ANSI-EI : A = 28.2,
B = 0.1217, P = 2.0
cha
r = DTL
t
d
, 1 % or 20ms
Reset time
ANSI DECAYING
Tm
R
t
Is
I
res
1
2
, 5 % absolute or 50 ms,
for char = ANSI-MI : R = 4.85
ANSI-VI : R = 21.6
ANSI-EI : R = 29.1
t
res
t
res
, 1 % or 20ms
Repeatability
1 % or 20ms
Overshoot time
< 40 ms
Disengaging time
< 60 ms
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......