Chapter 3) 7SR242 Duobias Performance Specification
©2015 Siemens Protection Devices Limited
Chapter 3 Page 24 of 50
2.5
46NPS Negative Phase Sequence Overcurrent
2.5.1 Reference (46DT)
Parameter
Value
I
s
Setting
0.05, 0.06... 4.0
xIn
t
d
Delay setting
0.00, 0.01…20.00, 20.50… 100, 101… 1000, 1010…
10000, 10100… 14400 s
2.5.2 Operate and Reset Level (46DT)
Attribute
Value
I
op
Operate level
100 %
Is
, 5 % or 1%
In
Reset level
95 %
I
op
Repeatability
1 %
Transient overreach
(X/R 100)
-5 %
Variation
-10 °C to +55 °C
5 %
f
nom
- 3 Hz to
f
nom
+ 2 Hz
5 %
2.5.3 Operate and Reset Time (46DT)
Attribute
Value
t
basic
Element basic operate time
0 to 2 x
Is
: 40 ms, 10ms
0 to 5 xI
s
: 30 ms, 10ms
t
op
Operate time following delay
t
basic
+
t
d
, 1 % or 10ms
Repeatability
1 % or 10ms
Overshoot time
<40 ms
Disengaging time
< 60 ms
2.5.4 Reference (46IT)
Parameter
Value
char
Characteristic setting
IEC-NI, -VI, -EI, -LTI; ANSI-MI, -VI, -EI; DTL
Tm
Time Multiplier setting
0.025, 0.030… 1.6, 1.7… 5, 6… 100
I
s
Setting
0.05, 0.06… 2.5
xIn
t
d
Delay setting
0, 0.01… 20 s
t
res
Reset setting
ANSI DECAYING, 0, 1… 60 s
2.5.5 Operate and Reset Level (46IT)
Attribute
Value
I
op
Operate level
105 %
Is
, 4 % or 1%
In
Reset level
95 %
I
op
Repeatability
1 %
Variation
-10 °C to +55 °C
5 %
f
nom
- 3 Hz to
f
nom
+ 2 Hz
5 %
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......