Chapter 3) 7SR242 Duobias Performance Specification
©2015 Siemens Protection Devices Limited
Chapter 3 Page 22 of 50
2.3 37,37G Undercurrent
2.3.1 Reference
Parameter
Value
Is
37-n Setting
0.05, 0.10…5.0
xIn
t
d
37-n Delay setting
0.00, 0.01…20.00, 20.50… 100, 101… 1000, 1010…
10000, 10100… 14400 s
Is
37-n U/I Guard Setting
0.05, 0.10…5.0
xIn
Parameter
Value
Is
37G-n Setting
0.05, 0.10…5.0
xIn
t
d
37G-n Delay setting
0.00, 0.01…20.00, 20.50… 100, 101… 1000, 1010…
10000, 10100… 14400 s
2.3.2 Operate and Reset Level
Attribute
Value
I
op
Operate level
100 %
Is
, 5 % or 1%
In
Reset level
105 %
I
op
Repeatability
1 %
Variation
-10 °C to +55 °C
5 %
f
nom
- 3 Hz to
f
nom
+ 2 Hz
5 %
2.3.3 Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
1.1 to 0.5 x
Is
: 35 ms, 10ms
t
op
Operate time following delay
t
basic
+
t
d
, 1 % or 10ms
Repeatability
1 % or 10ms
Overshoot time
< 40 ms
Disengaging time
< 60 ms
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......