Chapter 3) 7SR242 Duobias Performance Specification
©2015 Siemens Protection Devices Limited
Chapter 3 Page 21 of 50
2.2 27/59 Under/Over Voltage
2.2.1 Reference
Parameter
Value
V
s
Setting
5, 5.5…200V
hyst
Hysteresis setting
0, 0.1… 80.0%
t
d
Delay setting
0.00, 0.01…20.00, 20.50… 100, 101… 1000, 1010…
10000, 10100… 14400 s
2.2.2 Operate and Reset Level
Attribute
Value
V
op
Operate level
100 %
Vs
, 1 % or 0.25V
Reset level
Overvoltage
= (100 % -
hyst
)
x
V
op,
1 %
Undervoltage
= (100 % +
hyst
)
x
V
op,
1 %
Repeatability
1 %
Variation
-10 °C to +55 °C
5 %
f
nom
- 3 Hz to
f
nom
+ 2 Hz
5 %
2.2.3 Operate and Reset Time
Attribute
Value
t
basicE
Element basic
operate time
Overvoltage
0 to 1.1 x
Vs
:
73 ms 10ms
0 to 2.0 x
Vs
: 63 ms 10ms
Undervoltage
1.1 to 0.5 x
Vs
: 58 ms 10ms
t
op
Operate time following delay
t
basic
+
t
d
, 1 % or 10ms
Repeatability
1 % or 10ms
Disengaging time
< 80 ms
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......