Chapter 3) 7SR242 Duobias Performance Specification
©2015 Siemens Protection Devices Limited
Chapter 3 Page 19 of 50
Section 2: Protection Functions
2.1 24 Over Fluxing
2.1.1 Reference (24DT)
Parameter
Value
V/f
s
Setting
0.10, 0.11… 2.0 x Nominal Voltage / Nominal Frequency
Hyst
Hysteresis setting
0, 0.1… 80.0%
t
d
Delay setting
0.00, 0.01…20.00, 20.50… 100, 101… 1000, 1010… 10000,
10100… 14400 s
2.1.2 Operate and Reset Level (24DT)
Attribute
Value
V/f
op
Operate level
100% x
V/f
s
, 2 % or 0.02
Reset level
95% of
V/f
op
Repeatability
1 %
Variation
-10 °C to +55 °C
5 %
2.1.3 Operate and Reset Time (24DT)
Attribute
Value
t
basic
Element basic operate time
0.9 to 1.1 x
V/f
s
:
400 ms 200ms
0.9 to 2.0 x
V/f
s
: 320 ms 200ms
t
op
Operate time following delay
t
basic
+
t
d
, 1 % or 200ms
Repeatability
1 %
Disengaging time
< 250ms
2.1.4 Reference (24IT)
Parameter
Value
t
reset
Reset setting
0, 1… 1000 s
2.1.5 Operate and Reset Level (24IT)
Attribute
Value
V/f
op
Operate level
100% x
V/f
s
, 2 % or 0.02
Reset level
95% of
V/f
op
Repeatability
1 %
Variation
-10 °C to +55 °C
5 %
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......