Chapter 3) 7SR242 Duobias Performance Specification
©2015 Siemens Protection Devices Limited
Chapter 3 Page 14 of 50
1.3.2.6
Fibre Optic Ethernet Data Communication Interface (IEC 61850 Option)
Attribute
Value
Physical Layer
Fibre Optic
Connectors
Duplex LC 100BaseF in acc. With IEEE802.3
Recommended Fibre
62.5/125 m glass fibre with Duplex-LC connector
Transmission Speed
100MBit/s
Optical Wavelength
1300nm
Bridgeable distance
2km
1.3.2.7
Electrical Ethernet Data Communication Interface (IEC 61850 Option)
Attribute
Value
Physical Layer
Electrical
Connectors
RJ45 100BaseF in acc. With IEEE802.3
Transmission Speed
100MBit/s
Test Voltage (with regard to socket)
500 VAC 50 Hz
Bridgeable distance
20m
1.3.3 Real Time Clock
1.3.3.1
Internal Clock
The specification below applies only while no external synchronisation signal (e.g. IRIG-B, IEC 60870-5-103) is
being received.
Attribute
Value
Accuracy (-40 to +85
o
C)
3.5 ppm (No auxiliary supply connected)
100 ppm (Auxiliary supply connected)
1.3.3.2
IRIG-B
Attribute
Value
Connector
BNC
Signal Type
IRIG-B 120, 122 or 123
Applied signal level
minimum 3 V, maximum 6 V, peak-to-peak
Signal : carrier ratio
3
Input Impedance
4k Ohms Approx.
Summary of Contents for 7SR242 Duobias
Page 1: ...Answers for energy 7SR242 Duobias Transformer Protection Relay Reyrolle Protection Devices ...
Page 2: ...2 ...
Page 4: ...4 ...
Page 6: ...6 www siemens com energy ...
Page 318: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 2 of 64 ...
Page 324: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 8 of 64 ...
Page 358: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 42 of 64 ...
Page 366: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 50 of 64 ...
Page 380: ... 2015 Siemens Protection Devices Limited Chapter 7 Page 64 of 64 ...
Page 381: ......