7SR18 Description Of Operation
Unrestricted Page 68 of 78
©2018 Siemens Protection Devices Limited
5.5
Trip / Close Circuit Supervision (74TCS & 74CCS)
The relay provides three trip circuit supervision elements and three close circuit supervision elements. All
elements are identical in operation and independent from each other allowing 3 trip and 3 close circuits to be
monitored.
One or more binary inputs can be mapped to
74TCS-n.
The inputs are connected into the trip circuit such that at
least one input is energised when the trip circuit wiring is intact. If all mapped inputs become de-energised, due to
a break in the trip circuit wiring or loss of supply an output is given.
The
74TCS-n Delay
setting prevents failure being incorrectly indicated during circuit breaker operation. This delay
should be greater than the operating time of the circuit breaker.
The use of one or two binary inputs mapped to the same Trip Circuit Supervision element (e.g. 74TCS-n) allows
the user to realise several alternative monitoring schemes.
Figure 5.5-1 Logic Diagram: Trip Circuit Supervision Feature (74TCS)
Figure 5.5-2 Logic Diagram: Close Circuit Supervision Feature (74CCS)
Summary of Contents for 7SR18 Solkor
Page 1: ...Energy Management 7SR18 Solkor Line Differential Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 93: ...7SR18 Configuration Guide Unrestricted Page 12 of 12 2015 Siemens Protection Devices Limited ...
Page 221: ...7SR181 Solkor Technical Manual Chapter 4 Page 2 of 80 2016 Siemens Protection Devices Limited ...
Page 225: ...7SR181 Solkor Technical Manual Chapter 4 Page 6 of 80 2016 Siemens Protection Devices Limited ...