7SR18 Description Of Operation
Unrestricted ©2018 Siemens Protection Devices Limited
Page 67 of 78
5.4
Broken Conductor (46BC)
The element calculates the ratio of NPS to PPS currents. Where the NPS:PPS current ratio is above
46BC
Setting
an output is given after the
46BC Delay
.
The Broken Conductor function can be inhibited from
Inhibit 46BC
A binary or virtual input.
46BC U/C Guard
A minimum load current.
46BC U/C Guard Setting (0.05, 0.1... 5x In)
Figure 5.4-1 Logic Diagram: Broken Conductor Function (46BC)