![Siemens 7SR18 Solkor Manual Download Page 241](http://html.mh-extra.com/html/siemens/7sr18-solkor/7sr18-solkor_manual_383100241.webp)
7SR181 Solkor Technical Manual
Chapter 4 - Page 22 of 80
© 2016 Siemens Protection Devices Limited
FUN
INF
Description
ASDU
COT
183
236
Measurand Max I
a,b,c,
V
an,bn,cn,
P, Q, V
ab,bc,ca
---
Ia Max (2.4x) (Window 1%)
Ib Max (2.4x) (Window 1%)
Ic Max (2.4x) (Window 1%)
Van Max
1
(1.2x) (Window 1%)
Vbn Max
2
(1.2x) (Window 1%)
Vcn Max
3
(1.2x) (Window 1%)
P Max (2.4x) (Window 1%)
Q Max (2.4x) (Window 1%)
Vab Max (1.2x) (Window 1%)
Vbc Max (1.2x) (Window 1%)
Vca Max (1.2x) (Window 1%)
9
Cyclic -
Refresh
rate 5
seconds
or value
change
greater
than
Window x
%.
3.4.3 Disturbance Recorder Actual Channel (ACC) Numbers
The following Disturbance Recorder channel numbers apply to this device.
FUN
ACC
Description
182
1 V1
182
2 V2
182
3 V3
182
5 Ia
182
6 Ib
182
7 Ic
182
8 Ig1
182
14 Remote-Ia
182
15 Remote-Ib
182
16 Remote-Ic
182
17 Remote-Ig1
Summary of Contents for 7SR18 Solkor
Page 1: ...Energy Management 7SR18 Solkor Line Differential Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 93: ...7SR18 Configuration Guide Unrestricted Page 12 of 12 2015 Siemens Protection Devices Limited ...
Page 221: ...7SR181 Solkor Technical Manual Chapter 4 Page 2 of 80 2016 Siemens Protection Devices Limited ...
Page 225: ...7SR181 Solkor Technical Manual Chapter 4 Page 6 of 80 2016 Siemens Protection Devices Limited ...