7SR18 Performance Specification
Unrestricted ©2018 Siemens Protection Devices Limited
Page
39 of
Section 3: Supervision Functions
3.1 46BC Broken Conductor
3.1.1 Reference
Parameter
Value
NPS to PPS ratio
20,21…100 %
t
f
Delay setting
0.03,04,20.0,20.1,100,101,1000,1010…..14400 s
3.1.2
Operate and Reset Level
Attribute
Value
I
curr
Operate level
100 %
I
set
±
5 %
Reset level
90 %
I
curr ,
±
5 %
Repeatability
±
1 %
Variation
-10 °C to +55 °C
≤
5 %
f
nom
± 5 %
harmonics to
f
cutoff
≤
5 %
3.1.3
Operate and Reset Time
Attribute
Value
t
basic
Basic operate time 1x In to 0 A
40 ms
Operate time
t
f
+
t
basic
,
±
1 % or
±
20 ms
Repeatability
±
1 % or
±
20 ms
Variation
f
nom
± 5 %
harmonics to
f
cutoff
≤
5 %