7SR18 Performance Specification
Unrestricted Page 38 of 44
©2018 Siemens Protection Devices Limited
2.12 87HS High-Set Differential
2.12.1
Reference
Parameter
Value
Setting
1, 2 … 30 xIn
Delay setting
0, 0.005… 60 s
2.12.2
Operate and Reset Level
Attribute
Value
I
op
Operate level
±
5 % of setting or
±
0.01In
Reset level
≥
95 % of I
OP
Repeatability
±
2 %
Transient overreach
≤
5 %
Variation
-10 °C to +55 °C
f
nom
- 3 Hz to
f
nom
+ 2 Hz
2.12.3
Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
> 1.1 xIn 30 ms to 50 ms (Typically 30 ms)
2.13 85 Inter-trip Element
2.13.1
Reference
Attribute
Value
Delay setting
0, 0.005… 60 s
2.13.2
Operate Time
Attribute
Value
Inter-trip base element operate time
10 ms + 20 ms