7SR10, 7SR11, 7SR12 Applications Guide
© 2018 Siemens Protection Devices Limited
Chapter 7 Page 32 of 41
4.2 Quick Logic Applications
4.2.1 Auto-Changeover Scheme Example
INCOMER 1
INCOMER 2
Start On-Load
Change-over
CB1
OPEN
VT1
VT2
CB1
CB2
CB3
BI 1
BO3
V 1
Vx
Start On-Load
Change-over
Busbar 1
Busbar 2
LOADS
LOADS
Panel Enable
Switch
BI 2
Figure 4-3 Example Use of Quick Logic
The MV installation illustrated above is fed from two incomers. To limit the substation fault level the busbar is run
with CB3 open. When a fault occurs on one of the incomers it is isolated by the circuit protection. To re-supply the
disconnected loads from the remaining incomer CB3 is closed.
If the line fault occurs on incomer 1 it must be confirmed that CB 1 has opened before CB3 can be closed. The
relay on incomer 1 confirms that a trip has been issued to CB1 (e.g. Binary Output 2), that CB 1 has opened (e.g.
Binary Input 1) and that no current flows in the circuit (e.g. 37-1 = Virtual 1):
Incomer 1 Relay is Configured:
CB1 Open auxiliary switch wired to BI 1
Trip output to CB1 = BO 2
OUTPUT CONFIG>OUTPUT MATRIX:
37-1
=
V1
OUTPUT CONFIG>OUTPUT MATRIX:
E1
=
BO3
CONTROL & LOGIC>QUICK LOGIC:
E1
=
O2.I1.V1
The output from Incomer 1 (Binary Output 3) relay is input to the relay on CB 3 (Binary Input 1). A panel switch
may be used to enable the On-Load Change-over scheme (Binary Input 2). Before Closing CB3 a check may be
made that there is no voltage on busbar 1 (27/59-1 = Virtual 1). CB 3 is closed from Binary Output 3.
CB3 Relay is Configured:
Panel switch (ON-Load Change-over Enabled) wired to BI2
OUTPUT CONFIG>OUTPUT MATRIX:
27/59-1
=
V1
OUTPUT CONFIG>OUTPUT MATRIX:
E1
=
BO3
CONTROL & LOGIC>QUICK LOGIC:
E1
=
I1.I2.V1
If required a time delay can be added to the output using the CONTROL & LOGIC > QUICK LOGIC:
E1
Pickup Delay
setting
.
Summary of Contents for 7SR10 Argus Series
Page 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Page 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Page 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Page 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Page 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Page 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Page 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...