7SR10, 7SR11, 7SR12 Applications Guide
© 2018 Siemens Protection Devices Limited
Chapter 7 Page 4 of 41
Section 1: Common Functions
1.1 Multiple Settings Groups
Alternate settings groups can be used to reconfigure the relay during significant changes to system conditions
e.g.
Primary plant switching in/out.
Summer/winter or day/night settings.
Switchable earthing connections.
Loss of Grid connection (see below)
Figure 1-1
Example Use of Alternative Settings Groups
RADIAL SUBSTATION
Start
generators
Select alternate
settings group
Local
Generation
Industrial system draws power from grid
system during normal operation
Relays normally use settings group 1
On loss of mains:
Local generation switched in.
Non essential loads tripped
Relays on essential circuits switched to
settings group 2 to reflect new load and
fault currents
Non-essential
loads
Trip non-essential loads
Summary of Contents for 7SR10 Argus Series
Page 1: ...7SR10 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 152: ...7SR10 Technical Manual Chapter 4 Page 2 of 78 2018 Siemens Protection Devices ...
Page 156: ...7SR10 Technical Manual Chapter 4 Page 6 of 78 2018 Siemens Protection Devices ...
Page 188: ...7SR10 Technical Manual Chapter 4 Page 38 of 78 2018 Siemens Protection Devices ...
Page 216: ...7SR10 Technical Manual Chapter 4 Page 66 of 78 2018 Siemens Protection Devices ...
Page 218: ...7SR10 Technical Manual Chapter 4 Page 68 of 78 2018 Siemens Protection Devices ...
Page 220: ...7SR10 Technical Manual Chapter 4 Page 70 of 78 2018 Siemens Protection Devices ...
Page 222: ...7SR10 Technical Manual Chapter 4 Page 72 of 78 2018 Siemens Protection Devices ...