Routing Options
LEDs BOs
BIs
Description
TL
(stored only with tripping)
X
Routing option TL (tripping stored) is only possible for the
switching object circuit breaker.
The output is saved with protection tripping. The contact
remains activated until acknowledged.
Control commands are not affected. A control command is
pending above the parameterized command period until
feedback has been successfully received.
Note:
You can realize the functionality of the Lockout (ANSI 86)
by storing the output relay with the routing option TL.
Resetting Stored Indications of the Function Group
You can configure indications of individual functions as "stored" in a function group. This type of configuration
can be used for LEDs as well as for output contacts. The configured output (LED or contact) is activated until it
is acknowledged.
The protection and the circuit-breaker function groups contain the block Reset LED FG. The block
Reset LED FG is visible only in the Information routing under the corresponding function group in DIGSI 5.
You use the binary input signal
>Reset LED
to reset the stored LEDs in the respective function group. The
configured outputs (contacts) are not reset.
Test Mode and Influence of Indications on Substation Automation Technology
If the test mode of the device or of individual functions is switched on, the SIPROTEC 5 device marks indica-
tions sent to substation automation technology station control system with an additional test bit. This test bit
makes it possible to determine that an indication was set during a test. Necessary reactions in normal opera-
tion on the basis of an indication can thus be suppressed.
3.1.10
3.1.11
System Functions
3.1 Indications
SIPROTEC 5, Overcurrent Protection, Manual
85
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...