The default setting is a reasonable compromise between measuring accuracy and pickup time. For a non-
sensitive setting (high threshold value), you can set the parameter
Measuring window
to a smaller value.
Stage Description
Description
Logic of the Stage
[lodfdtst-160113-01.tif, 1, en_US]
Figure 6-221
Logic Diagram of Rate of Frequency Change Protection
(1)
For the stage type df/dt rising, the value df/dt rising is used.
Frequency Rising/Falling
The stage df/dt falling is used to detect frequency falling and the stage df/dt rising is used to detect
frequency rising.
You set the threshold value as an absolute value. You define the frequency-change direction via the selected
stage type.
Blocking of the Stage
The following blockings reset the picked up stage completely:
•
Via the binary input signal
>Block stage
•
Via the undervoltage blocking when the voltage drops below the
Minimum voltage
6.35.4
6.35.4.1
Protection and Automation Functions
6.35 Rate of Frequency Change Protection
SIPROTEC 5, Overcurrent Protection, Manual
787
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...