Blocking the Stage
In the event of blocking, the picked up stage will be reset. The following blocking options are available for the
stage:
•
Via the binary input signal
>Block stage
from an external or internal source
•
Via the
Inactive
input from the function block General
Behavior on Leaving the Operating Range
The sampling frequency tracking makes a wide frequency-operating range possible. If the stage has picked up
before leaving the frequency-operating range, the pickup is maintained. The
Pickup
signal is reset when a
blocking condition becomes active.
Application and Setting Notes
Parameter:
Threshold
•
Default setting
(_:18151:3) Threshold
=
49.00 Hz
for f
rated
= 50 Hz
With the
Threshold
parameter, you define the underfrequency pickup value of the stage. The specific value
depends on the application and the total number of the stages applied in parallel.
Parameter:
Operate delay
•
Default setting
(_:18151:6) Operate delay
=
0.10 s
Set the
Operate delay
parameter for the specific application.
Parameter:
Dropout differential
•
Default setting
(_:18151:5) Dropout differential
=
20 mHz
With the
Dropout differential
parameter, you define the dropout threshold. For example, if you set the
Threshold
to 49.00 Hz and the dropout differential to 20 mHz, the stage drops out at 48.98 Hz.
Due to the high-precision frequency measurement, the setting value can remain at the default value of
20 mHz.
Parameter:
Operate & flt.rec. blocked
•
Default setting
(_:18151:2) Operate & flt.rec. blocked
=
no
With the
Operate & flt.rec. blocked
parameter, you can block the operate indication, the fault
recording, and the fault log.
Parameter:
f< stabilization counter
•
Default setting
(_:18121:113) f< stabilization counter
=
6
You can configure the
f< stabilization counter
parameter in the function block General.
With the
f< stabilization counter
parameter, you set the number of measurement cycles in which the
measured frequency value must be lower than the frequency threshold to meet the pickup condition. With
this setting, you can optimize the pickup-condition reliability versus the pickup time.
The measuring cycle time is 10 ms. With the default setting of
6
, the pickup time is the sum of the inherent
frequency measuring time (approx. 10 ms to 30 ms) plus the 6 times measuring repetition of 60 ms, which is
70 ms to 90 ms in total.
In order to avoid a wrong pickup in case of a phase jump, Siemens recommends setting the value of the
f<
stabilization counter
parameter not below 5.
6.34.4.2
Protection and Automation Functions
6.34 Underfrequency Load Shedding
782
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...