Due to the high-precision frequency measurement, the recommended setting value for the
Dropout
differential
can remain at 20 mHz. If in your application you wish a subsequent dropout of the tripping
stage, then increase the setting value of the dropout differential. For instance, if the pickup value (parameter
Threshold
) of the tripping stage is set to 49.8 Hz and the
Dropout differential
to 100 mHz, the
stage will drop out at 49.9 Hz.
Application example of the underfrequency protection
Frequency protection can be used for load shedding. The UCTE has defined a 5-stage plan for the Western
European power grid. The setting values of the stages are based on that plan (see table below).
Table 6-16
Stage Plan
Frequency
Activity
49.80 Hz
Alarm and activation of reserves following an established plan
49.00 Hz
Undelayed disconnection of 10 % to 15 % of the power system load
48.70 Hz
Undelayed disconnection of another 10 % to 15 % of the power system load
48.40 Hz
3rd load shedding stage. Another 15 % to 20 % of the power system load is
disconnected.
47.50 Hz
Power plants are decoupled from the electrical power system
For this application, 3 stages of the underfrequency protection are used. 2 of these stages are used for load
shedding. The following table shows a setting suggestion.
Stage
Caused by
Setting Values
At f
rated
= 50 Hz
At f
rated
= 60 Hz
Delay
f1<
Warning
49.80 Hz
59.80 Hz
10.00
f2<
1st load shedding
49.00 Hz
59.00 Hz
0.00
f3<
2nd load shedding
48.70 Hz
58.70 Hz
0.00
i
i
NOTE
This table shows one example of a possible frequency protection setting. The setting values can differ
depending on the application.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2311:101
General:Minimum voltage
3.000 V to 175.000 V
37.500 V
_:2311:109
General:Dropout differential
20 mHz to 2000 mHz
20 mHz
Stage 1
_:61:1
Stage 1:Mode
•
off
•
on
•
test
off
_:61:2
Stage 1:Operate & flt.rec.
blocked
•
no
•
yes
no
_:61:3
Stage 1:Threshold
40.00 Hz to 70.00 Hz
49.80 Hz
_:61:6
Stage 1:Operate delay
0.00 s to 600.00 s
10.00 s
Stage 2
_:62:1
Stage 2:Mode
•
off
•
on
•
test
off
6.33.5
Protection and Automation Functions
6.33 Underfrequency Protection
SIPROTEC 5, Overcurrent Protection, Manual
771
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...