Stage with Negative-Sequence Voltage
Description
Logic of a Stage
[lou23pol-090611-01.tif, 3, en_US]
Figure 6-189
Logic Diagram of the Stage: Overvoltage Protection with Negative-Sequence Voltage
Method of Measurement
The stage uses the average value of the negative-sequence voltage, which is calculated from the function
block General Functionality. For more information, refer to chapter
.
Blocking the Stage
In case of blocking, the picked up function is reset. The following blocking option is available for the function:
•
From an external or internal source via the binary input signal
>Block stage
Application and Setting Notes
Parameter: Threshold
•
Default setting
(_:271:3) Threshold
=
5.800 V
The parameter
Threshold
is set according to the definition of the negative-sequence system.
Specify the
Threshold
(pickup threshold) for the specific application.
The secondary voltage of the voltage transformer can be used if the voltage transformer is adapted to the
rated voltage. The value of the 10 % negative-sequence voltage at a 100 V rated secondary voltage is:
100 V / 1.73 * 0.1 = 5.77 V
6.26.4
6.26.4.1
6.26.4.2
Protection and Automation Functions
6.26 Overvoltage Protection with Negative-Sequence Voltage
SIPROTEC 5, Overcurrent Protection, Manual
717
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...