Functional Test of Transient Ground-Fault Protection
General
This function requires the correct polarity of the ground current IN and the neutral-point displacement voltage
VN respectively the zero-sequence voltage V0. For the direction test of these quantities, refer to chapter
11.3 Direction Test of Ground Quantities for Directional Ground-Fault Functions
The function is based on the evaluation of the transient in the zero-sequence system after the ground-fault
ignition.
For issuing the signal
(_:13021:302) Ground fault
, the following 2 conditions must be met:
•
There is a transient in the ground quantities.
•
The fundamental compoment of the zero-sequence voltage V0 exceeds the threshold
(_:13021:103)
V0> threshold value
.
The following 2 methods are available for testing of the signal
(_:13021:302) Ground fault
:
•
Replaying real transient ground-fault recordings to the device
•
Using secondary test equipment which allows to simulate transients ground faults
However, the setting of parameter
(_:13021:103) V0> threshold value
cannot be tested precisely
with the mentioned 2 methods, since this test requires a static V0. An easy way to test the setting is described
in the following.
Secondary Test
This test must be carried out by injecting static secondary quantities. The test equipment needs to be config-
ured in a way that it generates zero-sequence current 3I0 and zero-sequence voltage V0, which are injected to
the SIPROTEC 5 device. By carrying out a shot, for example, a status change from zero-sequence values of 0 A
and 0 V to the values not equal to zero, a transient is generated. The signal
(_:13021:302) Ground
fault
is issued as long as the static zero-sequence voltage of the 2nd state is greater than the set threshold.
As amplitude for the secondary 3I0, 100 mA is a suitable value. In this test, the directional result contained in
the signal
(_:13021:302) Ground fault
is not defined and relevant, since the task is to test the setting
of parameter
(_:13021:103) V0> threshold value
only.
For testing the threshold, shots must be carried out with a static V0 slightly below the threshold and slightly
above the threshold, for example, to 98 % and 102 % of the threshold value or to a threshold value of -0.2 V
and +0.2 V (the greater absolute deviation of the threshold value must be selected) .
Consider that the V0 threshold is defined according to the definition of the symmetrical components. A full
neutral-point displacement voltage VN of 100 V causes V0 = 57.7 V.
Example
•
(_:13021:103) V0> threshold value
= 15 V
•
3 shots from 0 to V0 = 14.7 V and 3I0 = 100 mA
No signal
(_:13021:302) Ground fault
is issued.
•
3 shots from 0 to V0 = 15.3 V and 3I0 = 100 mA
Signal
(_:13021:302) Ground fault
is issued
If the test result is not as expected, check the injected static V0 voltage via the operational measurement of
the device which contains the zero-sequence components.
11.8
Functional Tests
11.8 Functional Test of Transient Ground-Fault Protection
1386
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...