i
i
NOTE
With the
P, Q sign
parameter in the function block General, the sign of the following measured values
of the respective function group can be inverted (see Chapter
10.2 Structure of the Function
Structure of
the Function, section Inversion of Output-Related Measured and Statistical Values):
•
Minimum/maximum values of the active and reactive power:
Min:Ptotal, Max:Ptotal, Min:Qtotal, Max:Qtotal
•
Minimum/maximum values of the average values of the active and reactive power:
AverageMin:Ptotal, AverageMax:Ptotal, AverageMin:Qtotal, AverageMax:Qtotal
Application and Setting Notes for Minimum/Maximum Values
The minimum/maximum values functionality is not preconfigured. If you want to use the functionality, you
must load it from the library into the respective function group.
The following settings listed for the calculation of the minimum/maximum values can be set with DIGSI or at
the device. You find the setting parameters in DIGSI in the project tree under Settings > Device settings.
Parameter: Min/Max cyclic reset
•
Default setting:
(_:107) Min/Max cyclic reset
=
yes
Parameter Value
Description
Yes
Cyclical resetting of the minimum and maximum value memories is activated
No
Cyclical resetting of the minimum and maximum value memories is deactivated
None of the following parameters are visible
Parameter: Min/Max reset each
•
Default setting:
(_:108) Min/Max reset each
=
1 day
Parameter Value
Description
1 day to 365 days
Resetting of the minimum value and the maximum value, cyclically on all specified
days, for example each day (1 day)
Parameter: Min/Max reset minute
•
Default setting:
(_:109) Min/Max reset minute
=
0 min
Parameter Value
Description
0 min to 1439 min
Resetting the minimum value and the maximum value at the specified minute of the
day, which is stated in the parameter
Min/Max Reset takes place every
, for
example 0 min (= 00:00)
Parameter: Min/Max days until start
•
Default setting:
(_:110) Min/Max days until start
=
1 day
:
Parameter Value
Description
1 day to 365 days
Indication of when the cyclical reset procedure of the minimum values and
maximum values begins, for example in 1 day (after the parameterization)
10.6.2
Measured Values, Energy Values, and Supervision of the Primary System
10.6 Minimum/Maximum Values
1318
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...