Average Values
Function Description of Average Values
Average values can be formed based on different measurands:
•
Operational measured values
•
Symmetrical components
Through the settings, you can set how and when the average values are formed. The settings describe:
•
Time slot over which the average value is formed
(Parameter:
Average calc. interval
)
•
Update interval for the display of the average values
(Parameter:
Average update interval
)
•
Synchronization time for establishing the date of commencement updating information, for example, at
the top of the hour (hh:00) or at one of the other times (hh:15, hh:30, hh:45).
(Parameter:
Average synchroniz. time
)
Average values are formed through the following measurands:
•
Operational measured values except for phase-related ratings
•
Amounts of the symmetrical components
You reset the average value formation via the
•
Binary input >Reset average value
•
DIGSI
•
The integrated operation panel
i
i
NOTE
With the
P, Q sign
parameter in the function block General, the sign of the following measured values
of the respective function group can be inverted (see Chapter
10.2 Structure of the Function
Structure of
the Function, section Inversion of Output-Related Measured and Statistical Values):
•
Active power (total): P total
•
Reactive power (total): Q total
Application and Setting Notes for Average Values
The average value formation functionality is not preconfigured with the devices in the function group. If you
use the functionality, you must load it from the library into the respective function group.
The following settings listed for the calculation of the average values can be set with DIGSI and at the device.
You find the setting parameters in DIGSI in the project tree under Settings > Device settings.
Parameter: Average calc. interval
•
Default setting:
(_:104) Average calc. interval
=
60 min
Parameter Value
Description
1 min to 60 min
Time slot for averaging, for example 60 minutes
Parameter: Average update interval
•
Default setting:
(_:105) Average update interval
=
60 min
10.5
10.5.1
10.5.2
Measured Values, Energy Values, and Supervision of the Primary System
10.5 Average Values
1314
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...