Indication
Type
Group
Warning
Explanation
VI-3ph: Mess.Volt.Fail detected:
(_:300)
Failure
SPS
CFC
Measuring-voltage failure detected:
Check the exterior wiring.
Blocking: Appropriate functions are
either blocked definitely or the blocking
can be set individually.
Defect Severity 2
Faults of defect severity 2 are fatal device faults that lead to an immediate restart of the device (reset).
This occurs when the device data is corrupted (for example, RAM memory), if a restart prevents restoration of
data consistency. The device goes briefly out of operation, a failure is avoided.
Life contact
Is terminated during the restart
Red error LED
Is activated during the restart
i
i
NOTE
If the fault of defect severity 2 has not be been removed after 3 unsuccessful restarts (reset), the fault is
automatically assigned to defect severity 3. The device will automatically turn to the fallback mode.
Log
For every device error with a subsequent restart (reset), only the restart can be detected in the operational log.
The actual supervision indication is entered in the device-diagnosis log at the point in time of the fault detec-
tion and before the restart. These indications are recorded with a real-time stamp and are thus available for
later analyses. The device-diagnosis log contains expanded fault descriptions. There you also receive recom-
mendations of corresponding corrective measures for each detected device error.
You can find further information on handling the logs in chapter 3.
Overview of Errors
Number
Device-Diagnosis Log
826
Processor error on the base module:
If the fault occurs numerous times, contact the Customer Support Center.
830
FPGA hardware error on the base module:
Contact the Customer Support Center.
834
Memory error (short term):
Reset initiated.
3823
Program run error:
If the fault occurs numerous times, contact the Customer Support Center.
826
CPU overload:
If the fault occurs numerous times, contact the Customer Support Center.
Miscellaneous
Internal firmware error:
If the fault occurs numerous times, contact the Customer Support Center.
Defect Severity 3
Faults of defect severity 3 are fatal device faults that lead to device immediately going into the fallback mode.
The signal
(_:301) Device status
goes to the
Alarm
state. The
Warning
state is not supported for this
signal.
9.8.3
9.8.4
Supervision Functions
9.8 Error Responses and Corrective Measures
SIPROTEC 5, Overcurrent Protection, Manual
1301
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...