Parameter:
Moving contact (highest binary input)
•
Default setting
Moving contact (highest binary input)
=
no
If the tap position is not to be recognized as valid and accepted until the motor sliding contact signals that it
has reached the taps, then activate the
Moving contact (highest binary input)
option. If this
parameter is set, the new position is only labeled with an * when the moving contact drops out.
Parameter:
Software filter time
•
Default setting
Software filter time
=
1000 ms
With this parameter, you specify the
Software filter time
for capturing the tap position. The range of
values extends from 0 ms to 86400000 ms. Within this time, brief changes on the binary inputs are
suppressed.
Parameter:
Retrigger filter
•
Default setting
Retrigger filter
=
Yes
With this parameter, you switch retriggering of the filtering time by a position change on or off.
Parameter:
Indication timestamp before filtering
•
Default setting
Indication timestamp before filtering
=
no
With this parameter, you specify whether the hardware filtering time is accounted for in the time stamp of
position capture.
Parameter:
Chatter blocking
•
Default setting
Chatter blocking
=
no
With this parameter, you switch
Chatter blocking
on or off.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Tap changer
_:104
Tap changer:Check
switching authority
•
no
•
yes
yes
_:108
Tap changer:Control model
•
status only
•
direct w. normal secur.
•
SBO w. normal secur.
•
direct w. enh. security
•
SBO w. enh. security
SBO w. enh.
security
_:109
Tap changer:SBO time-out
0.01 s to 1800.00 s
30.00 s
_:110
Tap changer:Feedback
monitoring time
0.01 s to 1800.00 s
10.00 s
Tap changer
_:111
Tap changer:Maximum
output time
0.02 s to 1800.00 s
1.50 s
_:112
Tap changer:Supervision
behavior
•
off
•
warning
•
alarm block
alarm block
_:113
Tap changer:Motor supervi-
sion time
5 s to 100 s
10 s
8.8.3
Control Functions
8.8 Transformer Tap Changers
1192
SIPROTEC 5, Overcurrent Protection, Manual
C53000-G5040-C017-8, Edition 07.2017
Summary of Contents for 7SJ82
Page 8: ...8 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 38: ...38 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 60: ...60 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 186: ...186 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 194: ...194 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 966: ...966 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1072: ...1072 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1236: ...1236 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1306: ...1306 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1370: ...1370 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1404: ...1404 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1576: ...1576 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1614: ...1614 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...
Page 1634: ...1634 SIPROTEC 5 Overcurrent Protection Manual C53000 G5040 C017 8 Edition 07 2017 ...