7SG13 Delta P20064 FM1 Autoreclosing 

Section 1: Introduction 

1.1  Introduction 

This document covers the auto-reclose function and its features. A Diagrams and Parameters document which 
covers each individual model is available, which lists explicitly the functions that are provided and the manner in 
which they are connected. 

 

 79, 

Auto-Reclose 

Notes 

1. 

The following notational and formatting conventions are used within the remainder of this document: 

 Setting: 

Elem Setting name

 

 Setting 

value: 

value

 

  Alternatives: 

[1st] [2nd] [3rd] 

2. Separate sections of the User Manual describe how to set up and operate the protection equipment: apply 
configuration, settings and passwords, view instruments and set default instruments, and retrieve fault data. 

c

start

trip

Elem

 Starter

Elem

 Inhibit

Elem

 Reset Delay

c

Forward

Reverse

Elem

 Char Dir

Non-Dir

PhA Dir Blk

PhaseAFwd

Digital input signal (status
input) visible to user

Digital output signal (output
relay) visible to user

Digital signal not visible to
user, to/from another element

Setting block showing list of setting
values, with setting name. Appropriate
block is TRUE when setting selected;
other blocks are FALSE.

Digital signal not visible to
user, internal to this element

Ia

Analogue signal with signal
description

Common setting for multi-function block.

c

start

trip

Function blocks.

Individual function blocks are disabled
when associated control input (c) is
FALSE.

Common control input (c) for multi-
function block. All function blocks are
disabled when control input is FALSE.

P300017 Current Protection Functions / Key

&

And Gate

1

Or Gate

 

Figure 1-1 

Key to Functional Block Diagrams 

©2010 Siemens Protection Devices Ltd. 

 

P20064 Page 3 of 7 

Summary of Contents for 7SG13 Delta

Page 1: ...e be reproduced from this document unless Siemens Protection Devices Ltd consent While the information and guidance given in this document is believed to be correct no liability shall be accepted for any loss or damage caused by any error or omission whether such error or omission is the result of negligence or any other cause Any and all such liability is disclaimed 2010 Siemens Protection Device...

Page 2: ... 4 2 1 4 Manual Close 4 2 1 5 In Out Switching 5 2 1 6 Overall Control 5 2 1 7 CB Close Command pulse 5 2 1 8 CB Failed To Open and CB Failed to Close 5 2 1 9 CB Closed by Another Device 5 2 1 10 Indications 5 2 1 11 Trip and Reclose 5 2 1 12 Metering 6 2 1 13 Dead time and Reclaim Timing 6 2 1 14 Lockout 6 List of Figures Figure 1 1 Key to Functional Block Diagrams 3 2010 Siemens Protection Devic...

Page 3: ...start trip Elem Starter Elem Inhibit Elem Reset Delay c Forward Reverse Elem Char Dir Non Dir PhA Dir Blk PhaseAFwd Digital input signal status input visible to user Digital output signal output relay visible to user Digital signal not visible to user to from another element Setting block showing list of setting values with setting name Appropriate block is TRUE when setting selected other blocks ...

Page 4: ... for each of the 4 recloses 2 1 1 Protection Trip The protection element which trips the CB is used to prime and start the autoreclose sequence Internal protection elements that will start the A R are pre selected within the relay 2 1 2 Protection Starter If during a sequence the breaker is closed from another device and a fault is still on the system the starter element will be energised This is ...

Page 5: ...table to allow a range of CBs to be used The Close pulse will be terminated if any protection Starter picks up or a trip occurs This is to prevent Close and Trip Command pulses existing simultaneously A Close Onto Fault Output is given if a starter or trip picks up in the Close Pulse This can be independently wired to Lockout 2 1 8 CB Failed To Open and CB Failed to Close CB Failed To Open and CB ...

Page 6: ...he Reclose Block Delay due to a persistent Block signal not cleared At the end of the Sync Close Delay due to Synchronism not being achieved Once the Lockout condition has been reached it will be maintained until reset The following will reset lockout By a Manual Close command from fascia comms or a status input By a Reset Lockout signal provided there is no signal present that will cause Lockout ...

Page 7: ... Inputs A R In A R Out Extern A R Start Block Reclose Go To Lockout Trip And Reclose Trip and Lockout Reset Lockout Manual Close _ 1 for each status input 2 1 14 1 Specification Element Parameters The element will take the following parameters unless otherwise specified in the appropriate Diagrams and Parameters document Parameter Value tcycle Element cycle time 20 ms tsetting Timer settings Appli...