Parameter assignment
7.21 Rate (P700 and P701)
SITRANS Probe LR with mA/HART
Operating Instructions, 05/2019, A5E32337711-AC
59
7.21
Rate (P700 and P701)
Note
Factory settings are indicated by an asterisk (*) in the parameter tables, unless explicitly
described.
These parameters determine how material level changes are reported.
7.21.1
P700 Maximum fill rate
Allows you to further adjust the SITRANS Probe LR response to increases in the actual
material level (or an advance to a higher Failsafe Material Level, P071). P700 is
automatically updated whenever Measurement Response (P003) is altered.
Values
Range
0.0000 to 99999 m/min
Factory setting
0.1
Altered by
P003 Measurement response
Related parameters
P005 Units
P007 Span
P071 Failsafe material level
Enter a value slightly greater than the maximum vessel-filling rate, in Units (P005) or percent
of Span (P007) per minute.
P003 value
Meters/minute
1
0.1
2
1
3
10
7.21.2
P701 Maximum empty rate
Adjusts the SITRANS Probe LR response to decreases in the actual material level (or an
advance to a lower Failsafe Material Level, P071). P701 is automatically updated whenever
Measurement Response (P003) is altered.
Values
Range
0.0000 to 99999 m / min
Factory setting
0.1
Altered by
P003 Measurement Response
Related parameters
P005 Units
P007 Span
P071 Failsafe Material Level