Parameter assignment
7.18 mA output (P201 to P215)
SITRANS Probe LR with mA/HART
54
Operating Instructions, 05/2019, A5E32337711-AC
7.18.2.1
P210 4 mA setpoint (low output)
Note
P210 is used to set the 4 mA loop current for the HART common module.
Sets the process level corresponding to the 4 mA value. 4 mA always defaults to 0, and
P201 determines whether this is a Level, Space, Distance, or Volume measurement. Level
and Space are measured as a percentage of Span; Distance is measured as a percentage
of Empty.
①
Reference point
④
Empty
②
Span
⑤
Space
③
Level
⑥
Distance
Values
Range
–99999 to 99999
Default
0.000 m (set to 0% as defined by P201: mA
Output Function)
Related parameters
P201: mA Output Function
Enter the reading that is to correspond to a 4 mA output. Use percent or units, depending on
the setting for P051.