6.4
Unit selection
The device is delivered with totalizer and flow rate units in m and m
3
/h, respectively, as
standard. However, it is possible to manually configure the device to operate with other units.
Changing the units
1. Select "Device" → "Unit guide".
2. Select the new unit from the list.
3. Click on "Apply Change of Units".
Afterwards, the change must be stored into the transmitter via "Download to Device".
6.5
Output configuration
Pulse output can be configured as volume pulse, alarm or call-up. Default factory setting is with
output A enabled for forward flow and output B for alarm output.
Output configuration in SIMATIC PDM
Select "Output". The software window shows the parameters for output configuration. Each
parameter has its own guideline for selecting the correct parameter setting.
Commissioning
6.5 Output configuration
SITRANS FM MAG 8000
56
Operating Instructions, 03/2020, A5E03071515-AH