
Parameterizing
7.2 Parameterizing via the operator interface
PAC1020
Equipment Manual, 05/2020, L1V30610008B-01
53
Current input
Selection
Range
Factory
setting
CT PRIMARY
Primary current of the current transformers
1 … 99999 A
50 A
CT SECONDARY
Secondary current of the current transformers
•
1 A
•
5 A
5 A
DISPLAY RANGE
Display range setting
Freely adjustable
1 … 99999 A
50 A
•
CURRENT DIREC L1
•
CURRENT DIREC L2
•
CURRENT DIREC L3
Inverse evaluation of the current flow direction
separately for each phase.
•
ON: Direction of current flow is inverted.
The device interprets the current flow direc-
tion as opposite to the wiring.
•
OFF: The device interprets the current flow
direction to match the wiring.
OFF
DISPLAY I(n)
Display of I(n) current
•
ON: I(n) is displayed
•
OFF: I(n) is not displayed
ON
Summary of Contents for 7KM1020-0BA01-1DA0
Page 1: ......
Page 2: ......
Page 8: ...Table of contents PAC1020 6 Equipment Manual 05 2020 L1V30610008B 01 ...
Page 22: ......
Page 50: ...Operation 6 1 Device interface PAC1020 48 Equipment Manual 05 2020 L1V30610008B 01 ...
Page 77: ...Technical data 10 1 Labeling PAC1020 Equipment Manual 05 2020 L1V30610008B 01 75 ...
Page 78: ......
Page 93: ......
Page 94: ......