Commissioning
5.5 Applying the measuring current
PAC1020
Equipment Manual, 05/2020, L1V30610008B-01
41
5.5
Applying the measuring current
The device is designed for connection of current transformers with secondary currents of 1 A
and 5 A. It is only possible to measure alternating currents.
The current measuring inputs can each be loaded with 10 A continuously or with 100 A for
1 s.
DANGER
Open transformer circuits will result in electric shock and arc flash hazards.
Will cause death, serious personal injury, or equipment damage.
It is only possible to measure the current with external current transformers. Do
not
use
fuses for circuit protection. Do not open the secondary circuit of the current transformers
under load. Short circuit the secondary current terminals of the current transformer before
removing this device. Follow the safety instructions for the applied current transformers.
NOTICE
Alternating current measurement only
Use the device to measure alternating current only.
Direction of current flow
Please take account of the direction of current flow when connecting the current measuring
inputs. With inverse connection, the measured values are inverted and receive a negative
sign.
To correct the direction of current flow, it is not necessary to reverse the input terminals.
Instead, change the direction of current flow in the device settings.
You will find information about device settings in chapter Basic parameters (Page 52).
5.6
Checking the displayed measured values
Correct connection type
With the help of the table "Display of measured variables depending on the connection type
(Page 14)", check whether the measured variables are displayed in accordance with the
implemented connection type. Any deviation indicates a wiring fault or configuration error.
Summary of Contents for 7KM1020-0BA01-1DA0
Page 1: ......
Page 2: ......
Page 8: ...Table of contents PAC1020 6 Equipment Manual 05 2020 L1V30610008B 01 ...
Page 22: ......
Page 50: ...Operation 6 1 Device interface PAC1020 48 Equipment Manual 05 2020 L1V30610008B 01 ...
Page 77: ...Technical data 10 1 Labeling PAC1020 Equipment Manual 05 2020 L1V30610008B 01 75 ...
Page 78: ......
Page 93: ......
Page 94: ......