s
________________________________________________________________________________
Siemens Energy & Automation, Inc. 3333 Old Milton Parkway Alpharetta, GA 30202
5
Starter Selection
Table 3: In Line, 200 – 460 Volt starter ratings
HP
@
200V
HP @
230V
HP @
460V
Rated
Current
(Amps)
Overload
Range
(Amps)
Current Limit
Range
(Amps)
Manufacturer
Catalog
Number
-
5
10
18
6 – 25
24 – 85
72GG34AFP
5
7.5
15
22
8 – 30
28 – 103
72HG34AFP
7.5
10
20
28
10 – 39
36 – 135
72JG34AFP
7.5
10
25
35
13 – 49
45 – 166
72KG34AFP
10
15
30
42
15 – 57
53 – 196
72LG34AFP
15
20
40
55
20 – 75
70 – 257
72MG34AFP
20
25
50
68
24 – 93
87 – 319
72NG34AFP
25
30
60
80
29 – 112
104 – 382
72PG34AFP
In Line
Configuration
40
50
-
130
48 – 181
168 - 618
72RG32AFP
Table 4: In Line, 460 - 575 Volt starter ratings
HP
@
460V
HP @
575V
Rated
Current
(Amps)
Overload
Range
(Amps)
Current Limit
Range
(Amps)
Manufacturer
Catalog
Number
10
15
18
6 – 25
24 – 85
72GG35AFP
15 20 22 8
–
30 28
–
103
72HG35AFP
20
25
28
10 – 39
36 – 135
72JG35AFP
25
30
35
13 – 49
45 – 166
72KG35AFP
30
40
42
15 – 57
53 – 196
72LG35AFP
40
50
55
20 – 75
70 – 257
72MG35AFP
50
60
68
24 – 93
87 – 319
72NG35AFP
In Line
Configuration
60 75 80 29
–
112
104
–
382
72PG35AFP