6.4 Technical data
6-165
©
Siemens AG 2012 All Rights Reserved
SIMODRIVE 611 Configuration Manual (PJU) – 02/2012 Edition
6.4
Technical data
6.4.1
General information
The configuring of the infeed modules requires the performance data from the
Tables 6-9 and 6-10 and the following performance curves.
300
1
P/P
rated
V
line supply
[V]
320
340
360
380
400
420
440
460
480
0
P
max. block unregulated
P
max. sine
P
S6
P
rated
Fig. 6-9
Normalized power graph
Note
When connected to line supplies with voltage fluctuations below the rated volta-
ge, the infeed should be overdimensioned corresponding to the above diagram
(Fig. 6-9), otherwise this can lead to failures or defects.
Table 6-7
Power factory at the rated power without filter
Module
Operation on the line side
Factor
cos
ϕ
1)
Factor
λ
I/R
Sinusoidal current operation
cos
ϕ
0.98
λ
0.97
I/R
Squarewave current operation
cos
ϕ
0.98
λ
0.89
UE
–
cos
ϕ
0.87
λ
0.67
cos
ϕ
: The power factor only contains the basic fundamental
λ
: The power factor contains the basic fundamental and harmonic components
1) Is valid for sinusoidal current operation at the rated voltage without filter
Note
With line filter, when the converter is operating at partial load, a capacitive pha-
se shift occurs.
As line supplies in companies generally have an inductive phase shift, this ca-
pacitive component has a compensating effect in this line supply.
6 Infeed Modules