Value
● Content of metals in the hydrogen sulfide group (lead, antimo‐
ny, tin, bismuth, arsenic, copper, cadmium)
● Content of metals from the ammonium sulfide group (iron, co‐
balt, nickel, chrome, manganese)
● Content of sulfur chloride and nitrogen compounds
Not detectable
Content of oxidizable, organic substances
Max. a quantity equivalent to the
usage of 30 mg/l potassium per‐
manganate KMnO4
Ion exchanger
An ion exchanger is installed in the re-cooling unit. The ion exchanger is connected in the
deionized water circuit.
If the conductivity exceeds the permissible limits, then a message is output. In this case,
replace the filling in the ion exchanger with an original filling. If the conductivity continues to rise,
the re-cooling unit and drive are switched off. The ion exchanger is a consumable and is not
covered by the warranty.
Dirt filters
The re-cooling unit is equipped with several dirt filters
● A dirt filter with a sieve (mesh width: 0.5 mm) is located in front of the drive intake.
● A fine filter (mesh width: 0.05 mm) is located at the ion filter outlet.
● An air filter is fitted on the expansion tank.
that filter out dirt and contamination from the water circuit, thereby preventing the drive from
being damaged.
3.7.4
The external raw water circuit
The raw water flows through the heat exchanger. The heat exchanger cools the deionized
water.
Description
3.7 Re-cooling unit
SINAMICS PERFECT HARMONY GH150 6SL3825
34
Operating Instructions 05/2020
Summary of Contents for 6SL3825
Page 2: ...19 06 2020 09 58 V14 00 ...
Page 12: ...Table of contents SINAMICS PERFECT HARMONY GH150 6SL3825 12 Operating Instructions 05 2020 ...
Page 130: ...Spare parts SINAMICS PERFECT HARMONY GH150 6SL3825 130 Operating Instructions 05 2020 ...
Page 134: ...Service Support SINAMICS PERFECT HARMONY GH150 6SL3825 134 Operating Instructions 05 2020 ...
Page 140: ...Quality documents SINAMICS PERFECT HARMONY GH150 6SL3825 140 Operating Instructions 05 2020 ...
Page 145: ......