Parameters/address space
4.3 Address space
Communication module IO-Link Master CM 8xIO-Link (6ES7547-1JF00-0AB0)
Manual, 03/2019, A5E45488510-AA
21
4.3
Address space
Configuration options of the communication module IO-Link Master CM 8xIO-Link
The size of the input and output addresses of the IO-Link Master CM 8xIO-Link
communication module with firmware version V1.0 are 32 bytes per port in each case.
The following table provides an overview of the configuration options of the supported
address areas for I/O data:
Module configuration
IM 155-5 PN
BA
IM 155-5 PN
ST
IM 155-5 PN
HF
IM 155-5 DP
ST
S7-1500
CPU
8 byte inputs
8 byte outputs
X
X
X
X
X
16 byte inputs
0 byte outputs
X
X
X
X
X
16 byte inputs
16 byte outputs
X
X
X
X
X
24 byte inputs
16 byte outputs
X
X
X
X
X
32 byte inputs
32 byte outputs
X
X
X
X
X
40 byte inputs
32 byte outputs
X
X
X
-
X
64 byte inputs
64 byte outputs
X
X
X
-
X
72 byte inputs
64 byte outputs
-
X
X
-
X
128 byte inputs
128 byte outputs
-
X
X
-
X
136 byte inputs
128 byte outputs
-
X
X
-
X
240 byte inputs
240 byte outputs
-
X
X
-
X
The IO area defined for an ET 200MP limits the number of IO modules per station. The
interface module supports a maximum of 512 bytes for input and output data for all I/O
modules in the station. Exceptions are 2 interface modules: IM 155-5 PN BA, which only
supports 64 bytes, and IM 155-5 DP ST with a limit of 244 bytes per station.