Technical specifications

 

 

Technical specifications of the 

DIQ 16x24VDC/0,5A 8xM12

 IO-Link digital input/digital output 

module 

The following table shows the technical specifications as of the issue date. You can find a 

data sheet including daily updated technical specifications on the Internet 

(

https://support.industry.siemens.com/cs/de/en/pv/6ES7143-5AH00-0BL0/td?dl=en

). 

 

Article number

 

6ES7143-5AH00-0BL0

 

General information

 

  

Product type designation 

DIQ 16X24VDC/0.5A, 8XM12 

HW functional status 

FS01 

Firmware version 

V1.0.x 

Engineering with

 

  

 

IODD file 

Yes 

Supply voltage

 

  

Load voltage 1L+

 

  

 

Rated value (DC) 

24 V; Supply from 1Us+ of the IO-Link master 

 

permissible range, lower limit (DC) 

18 V 

 

permissible range, upper limit (DC) 

30 V 

 

Reverse polarity protection 

Yes; against destruction 

Load voltage 2L+

 

  

 

Rated value (DC) 

24 V; Supply from 2UA+ of the IO-Link master 

 

permissible range, lower limit (DC) 

20.4 V 

 

permissible range, upper limit (DC) 

28.8 V 

 

Reverse polarity protection 

Yes; Against destruction; encoder power supply 

outputs applied with reversed polarity, loads pick 

up 

Input current

 

  

Current consumption (rated value) 

20 mA; without load 

from load voltage 2L+, max. 

4 A; Maximum value 

Encoder supply

 

  

Number of outputs 

8; Supply from 2UA+ of the IO-Link master 

24 V encoder supply

 

  

 

Short-circuit protection 

Yes; per module, electronic 

 

Output current, max. 

0.7 A; Total current of all encoders (depending on 

IO-Link master supply via 2UA+) 

Power loss

 

  

Power loss, typ. 

4 W 

Summary of Contents for 6ES7143-5AH00-0BL0

Page 1: ......

Page 2: ...k digital input digital output module DIQ 16x24VDC 0 5A 8xM12 6ES7143 5AH00 0BL0 Equipment Manual 08 2021 A5E47926885 AB Preface ET 200AL IO Link I O modules Documentation Guide 1 Product overview 2 Wiring 3 Parameters address space 4 Interrupts diagnostic alarms 5 Technical specifications 6 Dimension drawing A ...

Page 3: ...ly by personnel qualified for the specific task in accordance with the relevant documentation in particular its warning notices and safety instructions Qualified personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens prod...

Page 4: ...O system ET 200AL IO Link I O modules are described there The information provided in this manual and in the system manual and function manuals supports you in commissioning the ET 200AL IO Link I O modules Changes compared to the previous version This manual contains the following changes compared to the previous version Supplements in the section Parameters Page 15 Update of the section Technica...

Page 5: ...ems machines and components should only be connected to an enterprise network or the internet if and to the extent such a connection is necessary and only when appropriate security measures e g firewalls and or network segmentation are in place For additional information on industrial security measures that may be implemented please visit https www siemens com industrialsecurity Siemens products a...

Page 6: ...ew 9 2 1 Properties 9 2 2 Operator controls and display elements 12 3 Wiring 13 3 1 Terminal and block diagram 13 3 2 Pin assignment 14 4 Parameters address space 15 4 1 Parameters 15 4 2 Explanation of the parameters 16 4 3 Address space 17 4 4 IODD parameters 17 5 Interrupts diagnostic alarms 18 5 1 Status and error displays 18 5 2 Interrupts 20 5 3 Diagnostics alarms 20 6 Technical specificatio...

Page 7: ...O modules Device information Equipment manuals contain a compact description of the module specific information such as properties wiring diagrams characteristics and technical specifications General information The function manuals contain detailed descriptions on general topics regarding the SIMATIC IO Link system You can download the documentation free of charge from the Internet https support ...

Page 8: ...Documentation area In addition your data is already filled out in support requests and you can get an overview of your current requests at any time You must register once to use the full functionality of mySupport You can find mySupport on the Internet https support industry siemens com My ww en documentation mySupport CAx data In the CAx data area of mySupport you can access the latest product da...

Page 9: ...s The topology overview automatically scans the PROFINET and all connected components The IO check is a fast test of the wiring and the module configuration of a plant You can find SIEMENS PRONETA on the Internet https support industry siemens com cs ww en view 67460624 SIMATIC S7 PCT The Port Configuration Tool PCT is PC based software for the parameter assignment of Siemens IO Link master module...

Page 10: ...4VDC 0 5A 8xM12 6ES7143 5AH00 0BL0 Equipment Manual 08 2021 A5E47926885 AB 9 Product overview 2 2 1 Properties Article number 6ES7143 5AH00 0BL0 View of the module Figure 2 1 View of the DIQ 16x24VDC 0 5A 8xM12 IO Link digital input digital output module ...

Page 11: ...and proximity switches Typical input delay of 3 ms Configurable diagnostics can be set for each module Digital outputs Rated load voltage 24 V DC Suitable for solenoid valves DC contactors and indicator lights Output current per output 0 5 A Configurable diagnostics can be set for each module Dimensions 45 x 159 mm Interface for IO Link and power supply M12 connector A coded Supply of the module e...

Page 12: ... following component can be ordered as spare part Identification labels The following components can be ordered as accessories Connectors Cables M12 sealing cap See also You can find more information on accessories in the Accessories spare parts section of the ET 200AL distributed I O system https support industry siemens com cs us en view 89254965 IO Link I O modules system manual ...

Page 13: ...rols and display elements The figure below shows the operator controls and display elements of the DIQ 16x24VDC 0 5A 8xM12 IO Link digital input digital output module DIAG LED display for the diagnostic status X10 to X17 Sockets for the input output signal PWR LED display for load voltage 2L X35 IO Link interface LED displays 0 to 15 for the channel status Figure 2 2 Operator controls and display ...

Page 14: ...1L Supply voltage 1L non switched Configured as outputs 1M Ground 1M non switched Configured as input 3 wire connection 2L Load voltage 2L switched Configured as output 2M Ground 2M switched Configured as input 2 wire connection 2US 24 V encoder supply DI DQ circuit 2L switched DIQn Input output signal Microcontroller DIQ LEDs channel status 0 15 green Monitoring DIAG Diagnostic status LED red gre...

Page 15: ...ctor X13 Input output signal DIQ9 Connector X14 Input output signal DIQ11 Connector X15 Input output signal DIQ13 Connector X16 Input output signal DIQ15 Connector X17 3 Ground 2M 4 Input output signal DIQ0 Connector X10 Input output signal DIQ2 Connector X11 Input output signal DIQ4 Connector X12 Input output signal DIQ6 Connector X13 Input output signal DIQ8 Connector X14 Input output signal DIQ...

Page 16: ...al Value Dec Hex Diagnostics Missing load volt age 2L Disable 0 0 Disable Module 131 1 Enable 255 FF Diagnostics Short circuit to ground Disable 0 0 Disable Module Short circuit of encoder supply or of the output to ground 131 2 Enable 255 FF Freely assignable channel 0 7 DI 0 0 DI Channel 131 3 10 DQ 255 FF Freely assignable channel 8 15 DI 0 0 DQ Channel 131 11 18 DQ 255 FF Reaction to CPU maste...

Page 17: ...t of an encoder supply or of an output to ground Freely assignable channel With this parameter you set whether the channel is to be operated as an input or output Reaction to CPU master STOP With this parameter you set the reaction of the channels configured as output of the digital input output module after a CPU master STOP Deactivate The digital output is de energized Keep last value The last v...

Page 18: ...f information for system integration Communication properties Device parameters with value range and default value Identification process and diagnostic data Device data Text description Image of the device Manufacturer logo The structure of the IODD is identical for all devices from all manufacturers The structure of the IODD is always represented in the same manner by the IO Link Configuration T...

Page 19: ...AB Interrupts diagnostic alarms 5 5 1 Status and error displays LED displays The figure below shows the LED displays status and error displays of the DIQ 16x24VDC 0 5A 8xM12 IO Link digital input digital output module Diagnostic status DIAG red green Channel status 0 to 15 green Load voltage 2L PWR green Figure 5 1 LED displays ...

Page 20: ...1 Error display of the DIAG LED DIAG LED Meaning Off No supply voltage 1L Flashes No data exchange with the IO Link Master e g wire break Firmware is loading On Module is currently exchanging data with the IO Link master and no module diagnostics Flashes Module is currently exchanging data with the IO Link master and module diagnostics LED channel status Table 5 2 LED channel status display LED ch...

Page 21: ...gital output module You can read out the diagnostics alarms for example from the status of the IO Link master You can evaluate the error codes with the user program Table 5 4 Diagnostics alarms their meanings and corrective measures Diagnostics alarm Error code Meaning Solution Short circuit1 0x7710 Short circuit of an encoder sup ply to ground Eliminate the short circuit Short circuit of an outpu...

Page 22: ...Yes Supply voltage Load voltage 1L Rated value DC 24 V Supply from 1Us of the IO Link master permissible range lower limit DC 18 V permissible range upper limit DC 30 V Reverse polarity protection Yes against destruction Load voltage 2L Rated value DC 24 V Supply from 2UA of the IO Link master permissible range lower limit DC 20 4 V permissible range upper limit DC 28 8 V Reverse polarity protecti...

Page 23: ...nal 1 11 to 30V Input current for signal 1 typ 3 mA Input delay for rated value of input voltage for standard inputs at 0 to 1 min 1 2 ms at 0 to 1 max 4 8 ms at 1 to 0 min 1 2 ms at 1 to 0 max 4 8 ms Cable length unshielded max 30 m Digital outputs Number of digital outputs 16 Parameterizable as DIQ Short circuit protection Yes per channel electronic Response threshold typ 0 7 A Limitation of ind...

Page 24: ...Size of process data input per module 2 byte Size of process data output per module 2 byte Supported IO Link profiles common profile Cable length unshielded max 20 m Connection of IO Link devices Port type B Yes Interrupts diagnostics status information Substitute values connectable Yes channel by channel parameterizable Alarms Diagnostic alarm Yes Parameterizable Diagnoses Short circuit Yes outpu...

Page 25: ...les Yes From FS01 Highest safety class achievable for safety related tripping of standard modules Performance level according to ISO 13849 1 PL d Category according to ISO 13849 1 Cat 3 SILCL according to IEC 62061 SILCL 2 Ambient conditions Ambient temperature during operation min 30 C max 55 C Connection method Design of electrical connection for the inputs and outputs M12 5 pin A coded Type of ...

Page 26: ...A 8xM12 6ES7143 5AH00 0BL0 Equipment Manual 08 2021 A5E47926885 AB 25 Dimension drawing A The figure below shows the dimension drawing of the DIQ 16x24VDC 0 5A 8xM12 IO Link digital input digital output module in front and side view Figure A 1 Dimension drawing ...

Reviews: