Interrupts/diagnostic alarms
5.2 Interrupts
IO-Link digital input/digital output module DIQ 16x24VDC/0,5A 8xM12 (6ES7143-5AH00-0BL0)
20
Equipment Manual, 08/2021, A5E47926885-AB
5.2
Interrupts
Diagnostic interrupts of the DIQ 16x24VDC/0,5A 8xM12 IO-Link digital input/digital output
module.
Diagnostic interrupt
The digital input/digital output module generates a diagnostic interrupt at the following
events:
•
Short-circuit of an encoder supply to ground, or
•
Short-circuit of an output to ground
•
Load voltage 2L+ missing or too low
5.3
Diagnostics alarms
For each diagnostic event, a diagnostics alarm is issued and the LED DIAG flashes red on the
digital input/digital output module.
You can read out the diagnostics alarms, for example, from the status of the IO-Link master.
You can evaluate the error codes with the user program.
Table 5- 4
Diagnostics alarms, their meanings and corrective measures
Diagnostics alarm Error code Meaning
Solution
Short circuit
1
0x7710
Short-circuit of an encoder sup-
ply to ground
•
Eliminate the short-circuit
Short-circuit of an output to
ground
0x7711
Load voltage 2L+
missing
2
0x5112
Load voltage 2L+ missing or too
low
•
Check the supply voltage
•
Check the module
1
= If a short-circuit of an encoder supply to ground is detected, the diagnostic alarm "Short-circuit" is
always output. This alarm is output even if all channels are configured as outputs.
2
= If you are using ET 200AL modules in connection with the ET 200SP distributed I/O system, the
diagnostic alarm "Load voltage missing" is displayed.
Summary of Contents for 6ES7143-5AH00-0BL0
Page 1: ......