Installation
7.8 Maintenance
SITOP UPS1600 / BAT1600 / UPS1100
226
Equipment Manual, 07.2021, A5E37775406-11-76
Note
When battery modules are connected in parallel, only the fuse of the battery module where
the battery is replaced must be removed. Before recommissioning the battery module in the
parallel circuit, all battery modules must be charged to the same level (to avoid very high
recharging currents).
Note
Dispose of old batteries in the discharged state according to the applicable regulations.
Note
After the battery has been correctly replaced, the calculated battery health is reset to 100 %.
7.8.3
Battery replacement SITOP UPS1100
See Figure 7-7 Maintenance (Page 227) and Figure 7-8 Wiring schematic (Page 227)
1.
Release screws
⑨
using a Torx T10 screwdriver.
2.
Open the cover.
3.
Press button
⑧
for at least 2 s.
LED
④
flashes
4.
Remove fuse
③
5.
Replace the batteries.
6.
Press the button for at least 2 s
LED
④
stops flashing and lights continuously.
7.
Insert the fuse.
8.
Close the cover (screw).
Pressing the button resets the following functions:
•
Operating hours counter
•
Buffer time counter
•
Summed charge current
•
Summed load current
•
Calculated capacity
•
Calculated battery status
Note
Replace the battery only in normal operation, not in backup operation.