SITOP PSU8200 3ph
Manual, 11.2014, C98130-A7638-A1-2-7629
43
Ambient conditions
8
6EP3436-8SB00-0AY0 (24 V/20 A)
6EP1437-3BA10 (24 V / 40 A)
Ambient temperature
•
Remark
-25°...+70° C with natural convection
In the range -25 ... 0 °C continuous starting at a rated input v/-10 % is possible.
The specified properties (see Technical data (Page 29)) are only guaranteed in the
0 …+70 °C range.
Tested according to:
•
EN 60068-2-1 cold
•
EN 60068-2-2 dry heat
•
EN 60068-2-78 humid heat, constant
•
EN 60068-2-14 temperature change
Transport and storage tem-
perature
-40 ... +85° C
Tests (packed for shipping) according to:
•
EN 60068-2-1 cold
•
EN 60068-2-2 dry heat
•
EN 60068-2-30 humid heat, cyclic
Humidity class
Climatic class 3K3 according to EN 60721,
without condensation
Climatic class 3K3 according to EN 60721,
without condensation
Mechanical stressing during
operation
Tested according to:
•
EN 60068-2-6 vibration, test Fc:
7 mm deflection in the range
5 ... 8.4 Hz
2 g acceleration in the range
8.4 ... 150 Hz
•
EN 60068-2-27 shock, test Ea:
acceleration 150 m/s
2
, test duration
11 ms
Tested according to:
•
EN 60068-2-6 vibration, test Fc:
0.075 mm deflection in the range
10 ... 58 Hz
1 g acceleration in the range
58 ... 150 Hz
•
EN 60068-2-27 shock, test Ea:
acceleration 150 m/s
2
, test duration
11 ms