Description, device design, dimension drawing
2.4 Status displays and signaling
SITOP PSU8200 3ph
12
Manual, 11.2014, C98130-A7638-A1-2-7629
2.4
Status displays and signaling
6EP3436-8SB00-0AY0 (24 V/20 A)
6EP1437-3BA10 (24 V / 40 A)
Operating display
④
LED green for "24 V O.K."
Yellow LED for overload in "constant current" mode
Red LED for latching shutdown in "shut down" mode
Signaling contacts (13, 14)
⑤
Relay contact (NO contact, contact
rating 30 V AC / 0.5 A, 0 V DC / 0.3 A,
30 V DC / 1 A) for "24 V O.K."
Relay contact (NO contact, rating
60 V DC / 0.3 A) for "24 V O.K."
Figure 2-5
Operating display and signaling
Signaling
6EP3436-8SB00-0AY0 (24 V/20 A)
6EP1437-3BA10 (24 V / 40 A)
Green LED lit
Signaling contact,
contacts 13-14 closed
Normal operation, output voltage
>20 V ±0.5 V
Normal operation, output voltage
>20 V ±0.5 V
LED off
Signaling contact,
contacts 13-14 open
(quiescent position)
No supply voltage
No supply voltage
Yellow LED lit
Signaling contact,
contacts 13-14 open
(quiescent position)
Overload, output voltage <20 V ±0.5 V
(only in "constant current" mode)
Overload, output voltage <20 V ±0.5 V
(only in "constant current" mode)
Yellow and green LED lights
Signaling contact,
contacts 13-14 closed
Phase failure, output voltage O.K.
-