Technical Manual

Decentralized Power Supply
JB 125C33, 160 mA, AC 110 – 277V

5WG1125-4CB33

January 2022

Product and Application Description

The  JB  125C33  junction  box  mount  decentralized
power  supply  provides  KNX  Bus  power  for  Gamma
and TRA installations.  The device mounts to,  or in,
USA 4-11/16” square deep junction box.  Power sup-
ply  has  integral  choke  to  support  KNX  data  tele-
grams.   Bus  short circuit protection includes visible
operation status indicators.
KNX S-Mode installations requires at least one power
supply per line segment, main line, and backbone. A
second  power  supply  can  be  added  to  handle  bus
loads  exceeding  160  mA.    Maximum  of  two  (2)
JB 125C33 can be wired in parallel for 320 mA bus
load. For larger KNX installations, DIN mount power
supplies are available from Siemens Gamma.
Note: If two (2) power supplies are operated in par-
allel on one bus line and if the overload LED is lit on
one power supply, then the bus configuration must
be changed until the overload display disappears on
all units.

KNX TP (twisted pair) installation is “Free-Topology,”
“T” taps are allowed. The distance between any bus
device and the closest power supply unit must not
exceed 350 m (380 yds).
The  power  supply  has  voltage  and  current  regula-
tion, therefore is short-circuit proof.  Short power dis-
ruptions can be bridged with a reserve interval of at
least 100 ms.
To  ensure  uninterrupted  network  operation,  sepa-
rate (120 - 277Vac) power circuit should be used.
Total  Room  Automation  (TRA)  with  DXR  Controller
can use 1 or 2 JB 125C33 power supplies to support
the  room  devices.    The  DXR  internal  power  supply
must be deactivated when external  power  supplies
are added to the  (KNX) PL-LINK bus, see DXR Tech-
nical Product Information for details.

Technical Specifications

Input voltage

• operation voltage: AC 110 - 277 V, 50...60Hz

Rated power consumption approx. 3 W

Output voltage

• rated voltage: DC 24 V (class 2)
• safety extra low voltage (SELV)
• permissible range: DC 21 ... 30 V

Output current

• rated current 160 mA
• short-circuit current: limited to 0.39 A

Backup interval

on input voltage failure: 

 100 ms at rated current

Display elements

•  1 RED LED: shorted-out bus line or device over-load
•  1 GREEN LED: KNX power ON, normal operation

Connections

KNX Bus:  screwless “Push-Connect” standard KNX
terminal block (red/black).  Connect can fit 4 pairs of
terminations
BUS Wire:  18-22 AWG (0.6…0.8 mm) solid core,
twisted, shielded wire - strip insulation 5 mm.

Siemens wire:  KNX-TSP20LC-CMP

Electrical safety

Degree of pollution (according to IEC 60664-1): 2
Type of protection (according to EN 60529): IP 20
Overvoltage category (according to IEC 60664-1): III
Bus: safety extra low voltage SELV DC 24 V
Device complies with: IEC 61558-2-16, EN 50491-3

Physical specifications

housing: plastic

dimensions (L x W x D):
length: 3.0 inch (76 mm)
width: 3.62 inch (92 mm)
depth: 1.76 inch (45 mm)

weight: approx. 8 oz (210 g)

fire load: approx. 4 MJ

Installation: in a junction box
(min. dimensions (L-W-D))
Length: 4 11/16 inch (119 mm)
Width: 4 11/16 inch (119 mm)
Depth: 2 1/8 inch (54 mm)

Electromagnetic compatibility

complies with
IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3,
EN 50491-5-2, EN 50491-5-3

Environmental specifications

Ambient operating temperature:
- 5 … + 45 °C (+ 23 ... + 113

F)

Storage temperature:
- 25 … + 70 °C (- 13 ... + 158

F)

Relative humidity (not condensing): 5 % …  95 %

Reliability

Failure rate: 159 FIT at 40 °C (104 °F)

Markings

KNX, UL, ULC, PLENUM RATED

Listings and Certifications

UL listed (E464611)

UL 916 Open Energy Management Equipment
UL 2043 Plenum Rated - Suitable for installation
in Air Handling or Plenum spaces

Electromagnetic compatibility

USA:
This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference,
and
(2) this device must accept any interference received,
including interference that may cause undesired op-
eration.
This equipment has been tested and found to comply
with the limits for a Class B digital device, pursuant to
part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful inter-
ference in a residential installation. This equipment
generates, uses, and can radiate radio frequency en-
ergy and, if not installed and used in accordance with
the instructions, may cause harmful interference to
radio communications. However, there is no guaran-
tee that interference will not occur in a particular in-
stallation. If this equipment does cause harmful inter-
ference to radio or television reception, which can be
determined by turning the equipment off and on, the
user is encouraged to try to correct the interference
by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and
  receiver.
- Connect the equipment into an outlet on a circuit
  different from that to which the receiver is con-
nected.
- Consult the dealer or an experienced radio/TV
  technician for help.
This device complies with Part 15 of the FCC rules.
Changes or modifications not expressly approved by
Siemens Schweiz AG could void the user’s authority
to operate the equipment.
United States representative:
https://new.siemens.com/us/en/products/building-
technologies/home.html

Canada:
CAN ICES-3(B)/NMB-3(B)

Reviews: