background image

 

 

 
 

 
 

Powermite 599 Series 

Technical Instructions

Document No. 155-196P25

VF 599-5

April 9, 2009

 

MT Series Terminal Unit 
Two-way Valves 

 

 

 

Siemens Building Technologies, Inc. 

Description 

The Powermite 599 Series ANSI Class 250 MT Series two-way valve bodies work with 
any MT Series pneumatic or electronic actuator with a 7/32-inch (5.5 mm) stroke. 

Features 

 

Direct coupled universal bonnet 

 

Choice of brass or stainless steel trim 

 

ANSI Leakage Class IV (0.01% of Cv)  

Application 

A typical application for the Powermite two-way valve is the control of hot or chilled 
water or low pressure (<15 psi with stainless steel trim only) steam for convectors, fan 
coil units, unit conditioners, radiation, reheat coils, and similar terminal units requiring 
an actuator that delivers a minimum of 67 pounds force (300 N). 

Product Numbers 

See Table 2.  

Ordering a Valve 
Plus Actuator 
Assembly 

To order a complete valve plus actuator assembly from the factory, combine the 
actuator prefix code with the suffix of the valve assembly product number. See 

Technical Bulletin TB251

 (155-306P25) for selection procedure and ordering codes. 

Valve assemblies can be ordered using the numbers in Table 2. 

Specifications 

Valve size 

1/2 inch to 1 inch (15 mm to 25 mm) 

Capacity 

See Tables 3 through 6 and Figure 1

 

Body style 

Globe 

Seat style 

Metal-to-metal 

Action    

Normally open/normally closed 

Valve body rating  

ANSI Class 250; See Table 1 

Stem travel (Stroke) 

7/32-inch (5.5 mm) 

Summary of Contents for 599-02000

Page 1: ...y steam for convectors fan coil units unit conditioners radiation reheat coils and similar terminal units requiring an actuator that delivers a minimum of 67 pounds force 300 N Product Numbers See Table 2 Ordering a Valve Plus Actuator Assembly To order a complete valve plus actuator assembly from the factory combine the actuator prefix code with the suffix of the valve assembly product number See...

Page 2: ...e Table 1 Maximum recommended differential pressure for modulating service Brass trim Stainless steel trim Liquid 25 psi 173 kPa 50 psi 345 kPa Steam 15 psi 103 kPa Rangeability Cv 1 50 1 Cv 1 100 1 Close off pressures See Tables 7 and 8 and Figure 2 Close off ratings According to ANSI FCI 70 2 Leakage rate Class IV 0 01 of Cv Flow characteristics Modified equal percentage Miscellaneous Canadian R...

Page 3: ...2016 599 02000 599 02001 0 63 0 54 1 2 15 599 02017 599 02018 599 02002 599 02003 1 0 0 85 1 2 15 599 02019 599 02020 599 02004 599 02005 1 6 1 37 1 2 15 599 02021 599 02022 599 02006 599 02007 2 5 2 15 1 2 15 599 02023 599 02024 599 02008 599 02009 4 0 3 44 1 2 15 599 02025 599 02026 599 02010 599 02011 6 3 5 43 3 4 20 599 02027 599 02028 599 02012 599 02013 10 8 6 1 25 599 02029 599 02014 Normal...

Page 4: ...9 10 9 12 6 14 1 15 4 17 8 20 24 28 32 35 40 45 49 55 1 10 14 1 17 3 20 22 24 28 32 39 45 50 55 63 71 77 87 Table 4 Maximum Water Capacity Cubic Meters per Hour m3 hr Valve Size Pressure Differential kPa In mm 1 10 20 30 40 50 60 80 Kvs 100 150 200 300 400 500 15 0 03 0 11 0 15 0 19 0 22 0 24 0 26 0 30 0 34 0 42 0 48 0 59 0 68 0 76 0 05 0 17 0 24 0 30 0 34 0 38 0 42 0 48 0 54 0 66 0 76 0 94 1 08 1...

Page 5: ... 0 12 0 16 6 13 0 18 2 22 25 28 20 28 34 38 42 38 45 50 54 1 6 19 1 27 21 29 35 40 44 33 45 54 61 67 60 72 80 86 2 5 30 42 33 45 55 62 69 51 71 85 96 104 94 112 125 135 4 48 67 52 73 88 100 110 82 113 136 153 167 150 179 200 216 3 4 6 3 75 105 82 114 138 157 174 129 178 213 241 263 237 282 316 341 1 10 120 166 130 182 219 250 275 204 283 339 382 417 376 447 501 541 Table 6 Steam Capacity Kilograms...

Page 6: ... 5 1 2 15 Cv 1 6 1 2 15 Cv 1 0 1 2 15 Cv 0 63 1 2 15 Cv 0 4 8 9 10 20 30 40 50 60 70 80 90 100 200 300 400 100 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 0 5 0 4 0 3 0 2 0 1 0 6 0 8 1 1 2 3 4 5 6 8 10 20 30 40 50 60 80 100 200 300 1 10 2 1 0 8 0 6 0 5 0 4 0 3 0 2 0 1 0 08 0 06 0 05 0 04 0 03 3 4 5 6 8 20 30 40 50 10 VF0320R1 Figure 1 Water Capacity Graph Selection Example See Figure 1 Select a valve g...

Page 7: ...15 Kvs 3 44 3 4 20 40 276 40 276 1 25 NO 1 2 0 4 Cv 1 6 160 1103 120 828 15 0 34 Kvs 1 37 1 2 2 5 Cv 4 85 586 65 448 15 2 15 Kvs 3 44 3 4 20 70 482 55 379 1 25 Table 8 Maximum Available Close off Pressures for Pneumatic Actuators Action Valve Size Inch mm 2 inch Actuator 0 psi 0 kPa with 10 to 15 psi valve NC 1 2 0 4 Cv 1 6 95 655 15 0 34 Kvs 1 37 1 2 2 5 Cv 4 50 345 15 2 15 Kvs 3 44 3 4 20 40 276...

Page 8: ... 10 0 100 621 552 483 414 345 276 207 138 69 0 690 Line Size in Differential Pressure psi Differential Pressure kPa 65 448 120 828 55 379 2W NO SSC 1 2 Cv 0 4 Cv 1 6 1 2 Cv 2 5 Cv 4 3 4 and 1 120 100 80 60 40 20 0 140 828 690 552 414 276 138 0 996 50 345 95 655 40 276 90 80 70 60 50 40 30 20 10 0 100 621 552 483 414 345 276 207 138 69 0 690 Figure 2 Close off Pressures Operation Figure 3 shows the...

Page 9: ... with the actuator above the valve body The valve and actuator can be installed in any position between vertical and horizontal It is not recommended to install the valve assembly so that the actuator is below horizontal or upside down Allow sufficient space for servicing the valve and actuator See Table 11 for valve body dimensions See Figure 4 and Table 10 for dimensions of the service envelope ...

Page 10: ...25 April 9 2009 Page 10 Siemens Building Technologies Inc Service Replace the valve if inoperable Dimensions The letters in Figure 4 refer to the valve centerline to top of actuator the width of the actuator and service envelope dimensions in Table 10 See Table 11 for valve body dimensions Figure 4 ...

Page 11: ... 225 3 4 20 6 1 16 153 14 355 5 1 16 128 9 225 1 25 6 5 16 159 14 1 2 370 5 1 16 128 9 225 SQS85 53U Floating SR 266 1 2 15 6 1 16 153 14 355 5 1 16 128 9 225 3 4 20 6 1 16 153 14 355 5 1 16 128 9 225 1 25 6 5 16 159 14 1 2 370 5 1 16 128 9 225 SSC61U 0 to 10 Vdc NSR 261 1 2 15 5 1 2 140 13 1 2 343 4 3 4 121 12 3 4 324 3 4 20 5 1 2 140 13 1 2 343 4 3 4 121 12 3 4 324 1 25 5 3 4 146 13 3 4 349 4 3 ...

Page 12: ...ld Parkway Buffalo Grove IL 60089 4513 U S A Your feedback is important to us If you have comments about this document please send them to sbt_technical editor us sbt siemens com Document No 155 196P25 Country of Origin US Page 12 VF0218R1 C B A A VF0219R1 C B A D VF0220R1 C B D E Female NPT Female NPT F F Female NPT Union Male F UM Angle Female Union Male AF UM Table 11 2 way Valve Dimensions Val...

Reviews: